Single-Case Control Valve Sizing

Single-Case Control Valve Sizing Calculator

Single-Case Control Valve Sizing Calculator

Compute the required flow coefficient for liquid, gas and steam service using the ISA‑75.01.01 / IEC 60534‑2‑1 equations, with choked‑flow and cavitation checks.

Cv · Kv · Av  |  choked flow · cavitation · noise · valve selection
Service
Units

Water at 60°F = 1.0.

Absolute psi. Gauge = psig + 14.7.

Enter the pressure that actually exists at the valve outlet.

Valve & installation

FL and xT are typical published values — replace with the manufacturer’s data for final selection.

1.0 = plain pipe, no reducers.

Typically 1.10–1.25. Do not oversize.

Globe ≈ 50 (select 30 or 100). Other styles use their typical value: ball ≈ 100, butterfly ≈ 50, eccentric plug ≈ 50, angle ≈ 50.

Drives the pre-valve (inlet) pipe velocity at inlet pressure.

Internal bore & wall drive the IEC 60534‑8‑3 noise estimate (gas & steam only) and the post-valve (outlet) velocity. When the liquid flashes, the expanded two-phase volume raises the outlet velocity.

Rated‑Cv table used for the suggested size.

Pick the actual valve from the catalog; drives travel & characteristic.

Basis of calculation.
  • Liquid: Cv = (Q / (Fp · N1)) · √(Gf / ΔP), N1 = 1.0 (US units).
  • Liquid choking: ΔPchoked = FL² · (P1 − FF · Pv), with FF = 0.96 − 0.28√(Pv/Pc). Cavitation index σ = (P1 − FF·Pv) / ΔP, incipient cavitation at σ = 1.
  • Gas / steam: Cv = W / (N8 · Fp · P1 · Y · √(x·M / (T1·Z))), with N8 = 19.3 for lb/h · psia · °R and N8 = 94.8 for kg/h · bar · K.
  • Expansion factor Y = 1 − x / (3 · Fk · xT), Fk = k/1.4; choked when x ≥ Fk·xT, then Y = 0.667.
  • Kv = 0.865 · Cv  ·  Av = 2.40×10−5 · Cv
  • Water saturation pressure from the Wagner & Pruss correlation; vapor pressures of other liquids from Antoine coefficients.
  • Suggested body size comes from the Lapar rated‑capacity tables (High precision curve, Table 2 / High capacity curve, Table 3). The Table 2 lower‑half header reads “Port size(in)” but the values 65–300 are millimetres. FL, xT and Fd remain typical published values — confirm against the certified trim datasheet, plus actuator, materials and shut‑off class.

References: ANSI/ISA‑75.01.01‑2012 · IEC 60534‑2‑1:2011 · IEC 60534‑8‑3:2010 (aerodynamic) · IEC 60534‑8‑4:2015 (hydrodynamic) · Emerson/Fisher Control Valve Handbook 5th ed.

Related Articles